Menu
<br />
<b>Notice</b>:  Undefined index: alt_tags in <b>/home/vicintl/domains/vicinternational.nl/public_html/index.php</b> on line <b>161</b><br />

Multi protect foam

Low Thermal

Conductivity

0.021 W/mK
Thinner Insulation
Energy savings
Reduction of CO2 emissions

Excellent

Fire Behaviour

Euro class B/BL - S1 - D0
ASTM E84 25/50
No toxic fumes, no smoke

Variable

Densities

Range from 40 - 320 kg/m3

Closed Cell

Structure

Closed Cell > 95%

Large Range

Of Form Pieces

Pipe sections
T's, Elbows
Boards
Ducting
Sandwich panels

Advantages

Insulation Value

Multi Protect Foam is known for its high insulation performance. Its thermal conductivity has a typical value of 0.021 W/mK, which allows Multi Protect Foam to reduce the thickness in combination with a high thermal performance.

Fire Behaviour

Multi Protect Foam fulfills the international requirements for fire behaviour, and is tested according the worldwide norms like BSI, EN and ASTM for fire.
Multi Protect Foam achieves the highest possible values for phenolic insulation.

No Smoke and Non-toxic

Multi Protect Foam has an extreme low smoke emission (S1). No toxic fumes will be released by combustion.

Multi Protect Foam

Quality Assurance

Multi Protect Foam is accordingly tested in the in-house laboratory of the production facility as well by third party respected test institutes, to maintain and fulfill all requirements for the product to be used.

Closed Cell Structure

The closed cell structure of Multi Protect Foam, more than 95%, ensures no migration of moisture and internal condensation, this in contrast to other insulation materials with an open cell structure. This makes Multi Protect Foam very suitable for applications in the HVAC market.

Durability and Sustainability

Multi Protect Foam is 100% CFC and HCFC free and does not contain any flame retardant on the basis of halogens, the chloride content is lower than 5ppm and is no threat to the ozone layer depletion. The contribution of the greenhouse (Global Warming Potential) of Muliti Protect Foam is negligible.

Datasheets

40kg/m3
Properties Standard Typical value
Normal density EN 16-2 40 kg/m3 +/- 2
Thermal conductivity EN 12667 0.021 W/m.K +/- 0.002
Temperature limits -180 to +120 C
Specific heat 1.88 kl/kg. C
Compressive strength EN 826
- Paralellel to rise 180 kPa +/- 40
- Perpendicular to rise 180 kPa +/- 40
Tensile strength EN 1607
- Paralellel to rise 200 kPa +/- 40
- Perpendicular to rise 180 kPa +/- 40
Closed cell content EN ISO 4590 Minumum 95 %

Fire test classifications

• EN 13501-1 :2007 + A1 : 2009, EURO CLASS B/BL-S1-D0
• ASTM E84 25/50 Flame and Smoke

Equivalent to

• BS476 Part 6 and Part 7 – Class 0
• Epiradiateur – M1

• NEN 6065/6066 – Klasse 1/2
• DIN 4102 – B1

Other information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best knowledge of Vic International BV. The data on this sheet relates only to the specific material designated herein. Vic International BV assumes no legal responsibility for use or reliance upon this data. For information regarding specific applications of the product please contact Vic International BV.

60kg/m3
Properties Standard Typical value
Normal density EN 1602 60 kg/m3 +/- 2
Thermal conductivity EN 12667 0.024 W/m.K +/-0.002
Temperature limits   -180 to +120 C
Specific heat   1.88 kl/kg. C
     
Compressive strength EN 826
- Paralellel to rise 350 kPa +/- 40
- Perpendicular to rise 275 kPa +/- 40
     
Tensile strength EN 1607
- Paralellel to rise 310 kPa +/- 40
- Perpendicular to rise 250 kPa +/- 40
     
Closed cell content EN ISO 4590 Minumum 95 %

Fire test classifications

• EN 13501-1 :2007 + A1 : 2009, EURO CLASS B/BL-S1-D0
• ASTM E84 25/50 Flame and Smoke

Equivalent to

• BS476 Part 6 and Part 7 – Class 0
• Epiradiateur – M1

• NEN 6065/6066 – Klasse 1/2
• DIN 4102 – B1

Other information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best knowledge of Vic International BV. The data on this sheet relates only to the specific material designated herein. Vic International BV assumes no legal responsibility for use or reliance upon this data. For information regarding specific applications of the product please contact Vic International BV.

80kg/m3
Properties Standard Typical value
Normal density EN 1602 80 kg/m3 +/- 2
Thermal conductivity EN 12667 0.030 W/m.K +/-0.002
Temperature limits   -180 to +120 C
Specific heat   1.88 kl/kg. C
     
Compressive strength EN 826
- Paralellel to rise 620 kPa +/- 40
- Perpendicular to rise 480 kPa +/- 40
     
Tensile strength EN 1607
- Paralellel to rise 550 kPa +/- 40
- Perpendicular to rise 400 kPa +/- 40
     
Closed cell content EN ISO 4590 Minumum 95 %

Fire test classifications

• EN 13501-1 :2007 + A1 : 2009, EURO CLASS B/BL-S1-D0
• ASTM E84 25/50 Flame and Smoke

Equivalent to

• BS476 Part 6 and Part 7 – Class 0
• Epiradiateur – M1

• NEN 6065/6066 – Klasse 1/2
• DIN 4102 – B1

Other information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best knowledge of Vic International BV. The data on this sheet relates only to the specific material designated herein. Vic International BV assumes no legal responsibility for use or reliance upon this data. For information regarding specific applications of the product please contact Vic International BV.

120kg/m3
Properties Standard Typical value
Normal density EN 1602 120 kg/m3 +/- 2
Thermal conductivity EN 12667 0.032 W/m.K +/-0.002
Temperature limits   -180 to +120 C
Specific heat   1.88 kl/kg. C
     
Compressive strength EN 826
- Paralellel to rise 1050 kPa +/- 40
- Perpendicular to rise 760 kPa +/- 40
     
Tensile strength EN 1607
- Paralellel to rise 700 kPa +/- 40
- Perpendicular to rise 620 kPa +/- 40
     
Closed cell content EN ISO 4590 Minumum 95 %

Fire test classifications

• EN 13501-1 :2007 + A1 : 2009, EURO CLASS B/BL-S1-D0
• ASTM E84 25/50 Flame and Smoke

Equivalent to

• BS476 Part 6 and Part 7 – Class 0
• Epiradiateur – M1

• NEN 6065/6066 – Klasse 1/2
• DIN 4102 – B1

Other information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best knowledge of Vic International BV. The data on this sheet relates only to the specific material designated herein. Vic International BV assumes no legal responsibility for use or reliance upon this data. For information regarding specific applications of the product please contact Vic International BV.